Daikin EWAD495TZPLB2 handleiding

84 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 28 van 84
Air cooled inverter water chiller
OPERATION
MANUAL
Operation Manual
28
EWAD TZ B 160-700
Air cooled inverter water chiller
D-EOMAC00909-16EN
4.2.5.5 Standby Chiller
This menu allows to configure the standby chiller
Setpoint/Sub-
Menu
Default
Range
Description
Standby Chiller=
No
No, Auto, Master, Slave 1, Slave 2,
Slave 3
Standby chiller selection
Cycling Type=
Time
Run Hours, Sequence
Cycling type of standby chiller if previous parameter Standby
Chiller is set as Auto
Interval Time=
7 Days
1…365
Define the interval time (expressed in day) for the cycling of
standby chiller
Switch Time=
00:00:00
00:00:00…23:59:59
Define the time within the day when will be performed the
switch of the standby chiller
Tmp Cmp=
No
No,Yes
Enabling of Temperature Compensation function
Tmp Comp Time=
120 min
0…600
Time constant of Temperature Compensation function
Standby Reset=
Off
Off, Reset
Parameter to reset standby chiller cycling timer
4.2.6 Rapid Restart
This page shows if the function Rapid Restart is enabled by external contact and it allows to define
the maximum black out time in order to recover quickly the unit load.
Setpoint/Sub-Menu
Default
Range
Description
Rapid Restart=
Disable
Enable, Disable
Feature enable if Rapid Restart is installed
Pwr Off Time=
60s
-
Maximum black out time to enable Rapid Restart
4.2.7 Date/Time
This page will allow to adjust the time and date in the UC. This time and date will be used in the
alarm log and to enable and disable the Quiet Mode. Additionally it’s also possible to set the
starting and ending date for the DayLight Saving time (DLS) if used.
Quiet Mode is a feature that is used to reduce the chiller noise. This is done by applying the
maximum setpoint reset to the cooling setpoint and increasing the condenser temperature target
by an adjustable offset.
Setpoint/Sub-Menu
Default
Range
Description
Actual Time=
12:00:00
Actual Date=
01/01/2014
UTC Diff=
-60min
Difference with UTC
DLS Enable=
Yes
No, Yes
DLS Strt Month=
Mar
DayLight Saving time start month
DLS Strt Week=
2ndWeek
DayLight Saving time start week
DLS End Month=
Nov
NA, Jan…Dec
DayLight Saving time end month
DLS End Week=
1stWeek
1
st
…5
th
week
DayLight Saving time end week
Quiet Mode=
Disable
Disable, Enable
Activate Quiet Mode
QM Start Hr=
21h
18…23h
Quiet Mode start hour
QM Start Min=
0min
0…59min
Quiet Mode start minute
QM End Hr=
6h
5…9h
Quiet Mode end hour
QM End Min=
0min
0…59min
Quiet Mode end minute
QM Cond Offset=
5°C
0.0…14.0°C
Quiet Mode condenser target offset
On board real time clock settings are maintained thanks to a battery mounted on the controller.
Make sure that the battery is replaced regularly each 2 years (see section 3.6).