BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-
23_01EN_EWAD/H_EWFD/H -
T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 9 / 53
Software name:
ETRA / OMEGA
Unit Support
English
NC Dev 1
0
NC Dev 2
0
(1) Verify whether DHCP should or should not be enabled. If not, obtain the IP Subnet Mask of
the shared network from the network administrator. Then, obtain static IP Addresses for all
MicroTech Unit Controllers you are integrating into the shared network. Finally, obtain the
address of an IP Router to use for sending IP messages to and from the BACnet IP subnets.
(2) These addresses are used if DHCP (Dynamic Host Configuration Property) is set to Off. For
changes to these parameters to take effect, use the keypad/display and set Apply Changes
on the BACnet IP Setup menu to Yes. This will cause the power on the unit controller to reset.
4.3 BACnet MS/TP module (POL904.00/STD)
Module
description
Part
Description
1
Interface RS485, plug-in terminals with screw/terminal connections.
2
Status display BSP (Board Support Package).
3
Status display BUS (bus connections / bus traffic o.k.).
4
Plug connection Communication extension bus.
5
Microtech controller.
BSP Led
Color
Flashing frequency
Meaning
Green
Steady on
BSP operating and communication with
controller working.
Yellow
Steady on
BSP operating, but no communication with
controller.
Red
Steady on
Hardware fault.
Red/Yellow
Flashing at 1 Hz
(1 second on/ 1 second off)
Upgrade mode running.
Red
Flashing at 2 Hz
(0,5 second on/ 0,5 second
off)
BSP error (software error).
BUS Led
Color
Flashing frequency
Meaning
Green
Steady on
Communication active.
Yellow
Steady on
Initializing
Red
Steady on
Communication interrupted.
Module
connection
Step
Action
1
Power off the controller
2
Connect POL904 module to the controller via plug connection (part 4).
3
Connect the TCP/IP bus cable to the POL908.
4
Power on the controller
Configuration
procedure
Step
Action
1
Check that BUS led status is steady on green coloured.
2
Navigate the unit’s keypad/display to the main menu page and set the “service” password
3
Navigate the unit’s keypad/display following the path below:
Main menuCommissioningBACnetMSTP Setup
4
Set parameters in the table below as needed according to the local network