BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 35 / 53
Software name:
ETRA / OMEGA
CODE
INDEX
LEVEL
Device
Description
36423
Fault
C2.Comp1
36427
Fault
C2.Comp2
36387
142
Fault
Circuit 1
CIRCUIT SHUTDOWN - Condenser Pressure Sensor Fault #n
36419
Fault
Circuit 2
36611
143
Fault
Unit
UNIT SHUTDOWN - Condenser Water Flow Loss
36867
144
Fault
Unit
UNIT SHUTDOWN - Condenser Pressure High
37155
145
Fault
Circuit 1
CIRCUIT SHUTDOWN - Condenser Pressure High #n
37187
Fault
Circuit 2
37415
146
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - Current High with Compressor OFF #n
37419
Fault
C1.Comp2
37447
Fault
C2.Comp1
37451
Fault
C2.Comp2
37671
147
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - Discharge Temperature Sensor Fault #n
37675
Fault
C1.Comp2
37703
Fault
C2.Comp1
37707
Fault
C2.Comp2
37927
148
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - Discharge Temperature High #n
37931
Fault
C1.Comp2
37959
Fault
C2.Comp1
37963
Fault
C2.Comp2
38147
149
Fault
Unit
UNIT SHUTDOWN - Condenser Entering Water Temperature Sensor Fault
38403
150
Fault
Unit
UNIT SHUTDOWN - Evaporator Water Flow Loss
38659
151
Fault
Unit
UNIT SHUTDOWN - Evaporator LWT or EWT Low (Freeze)
38915
152
Fault
Unit
UNIT SHUTDOWN - Evaporator Pressure Low
39207
153
Fault
C1.Comp1
COMPRESSOR SHUTDOWN - Evaporator (or Suction) Pressure Low #n