Daikin EWAD380TZXSD1 handleiding

53 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 29 van 53
BAS Integration Guide-BACnet protocol
Document name:
D-EIGOC00103-23_01EN_EWAD/H_EWFD/H
-T/MZD
Product name:
EWAD/H-T/MZD & EWFD/H-
T/MZD
Page 29 / 53
Software name:
ETRA / OMEGA
CODE
INDEX
LEVEL
Device
Description
1869
Warning
C2.Comp3
2049
8
Warning
Unit
Bad setpoint override input
2305
9
Warning
Unit
Bad demand limit input
2561
10
Warning
Unit
Power Loss While Running
2817
11
Warning
Unit
Unit Power Restore
3105
12
Warning
Circuit 1
Circuit Failed Pumpdown
3137
Warning
Circuit 2
3329
13
Warning
Unit
External Event
3585
14
Warning
Unit
Bad Current Limit Input
3841
15
Warning
Unit
Option Controller Communication Failed
4128
16
Warning
Circuit 1
Low Refrigerant Charge
4160
Warning
Circuit 2
4352
17
Warning
Unit
Chiller network Communication Failure
6177
24
Warning
Circuit 1
Economizer Pressure Sensor Fault #n
6209
Warning
Circuit 2
6433
25
Warning
Circuit 1
Economizer Temperature Sensor Fault #n
6465
Warning
Circuit 2
6689
26
Warning
Circuit 1
Economizer EXV Motor Fault
6721
Warning
Circuit 2
7201
28
Warning
Circuit 1
Economizer EXV Module Communications Fault
7233
Warning
Circuit 2
7461
29
Warning
C1.Comp1
Hot Gas Bypass Fault
7465
Warning
C1.Comp2
7493
Warning
C1.Comp1
7497
Warning
C1.Comp2

Bekijk gratis de handleiding van Daikin EWAD380TZXSD1, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelEWAD380TZXSD1
CategorieAirco
TaalNederlands
Grootte5821 MB