4.6.1. Version identification
To identify unambiguously the software class and version (also with respect to other Daikin
control software) a string made of four fields is used:
C
1
C
2
C
3
F
M
M
m
A three-digit literal
field (C
1
C
2
C
3
) to identify the class of units for which the software is usable
The first digit C
1
is for chillers cooling type and will assume the following values:
- A : for air cooled chillers
- W : for water cooled chiller
The second digit C
2
is for compressor type and will assume the following values:
- S : for screw compressors
- R : for reciprocating compressors
- Z : for scroll compressors
- C : for centrifugal compressors
- T : for turbocor compressors
The third digit C
3
is for evaporator type and will assume the following values:
- D : for direct expansion evaporator
- R : for remote direct expansion evaporator
- F : for flooded evaporator
• A single-digit literal (F) field to identify the unit family
Within the scope of this document (screw chillers identified by C
2
field) it will assume
the following values
- A : Frame 3100 family
- B : Frame 3200 family
- C : Frame 4 family
- U : when the software is applicable to all families within the class
• A major version two-digit numeric field (MM)
• A minor version single-digit literal field (m)
Within the scope of this document the first version is :
ASDU01C
Any version is also identified by a release date.
The first three digits of the version string will never be changed (otherwise a new unit class,
and consequently a new software is released).
The fourth digit will change if a family-specific feature is added and it is not applicable to
other families; in this case the U value may not be used anymore and a software for any family will
be released. When this happens the versions digit is reset to the lower value.
The major version number (MM) will increase any time a completely new function is
introduced in the software, or the minor version digit as reached the maximum allowed value (Z).
The minor version digit (m) is increased any time minor modification is introduced in the
software without modifying its main working mode (this includes bugs fixing and minor interface
modifications).
Engineering version, that meanings versions under tested, is identified adding to the version
string the letter E followed by a number digit identifying the progression of engineering versions.