Installation and operation manual
19
EUWY(*)5~24KBZW1
Packaged reversible air to water heat pumps
4PW61655-1 – 07.2010
TROUBLESHOOTING
This section provides useful information for diagnosing and
correcting certain troubles which may occur in the unit.
Before starting the troubleshooting procedure, carry out a thorough
visual inspection of the unit and look for obvious defects such as
loose connections or defective wiring.
Before contacting your local dealer, read this chapter carefully, it will
save you time and money.
When a safety device was activated, stop the unit and find out why
the safety device was activated before resetting it. Under no
circumstances safety devices may be bridged or changed to a value
other than the factory setting. If the cause of the problem cannot be
found, call your local dealer.
Symptom 1: The unit does not start, but the L LED lights up
Symptom 2: The unit does not start, but the
L LED is flashing
Symptom 3: The unit does not start and the
L LED does not light up
Symptom 4: One of the following safety devices is activated
When carrying out an inspection on the switch box of the
unit, always make sure that the main switch of the unit is
switched off.
POSSIBLE CAUSES CORRECTIVE ACTION
The temperature setting is not
correct.
Check the controller setpoint.
Power supply failure. Check the voltage on the supply
panel.
Blown fuse or interrupted protection
device.
Inspect fuses and protection
devices. Replace by fuses of the
same size and type (refer to chapter
"Electrical specifications" on
page 4).
Loose connections. Inspect connections of the field
wiring and the internal wiring of the
unit. Tighten all loose connections.
Shorted or broken wires. Test circuits using a tester and repair
if necessary.
POSSIBLE CAUSES CORRECTIVE ACTION
The flowstart timer is still running. The unit will start after approx. 15
seconds. Make sure the water is
flowing through the evaporator.
The remote ON/OFF input is
enabled and the remote switch is off.
Put the remote switch on or disable
the remote ON/OFF input.
The anti-recycling timer is still active. The cicuit can only start up after
approximately 4 minutes.
The guard timer is still active. The circuit can only start up after
approximately 1 minute.
POSSIBLE CAUSES CORRECTIVE ACTION
One of the following safety devices is
activated:
•Reverse phase protector
•Overcurrent relay (K*S)
Discharge thermal protector (Q*D)
•Evaporating temperature
Thermostat (S*T)
Flow switch (S10L)
High pressure switch (S*HP)
Check on the controller and refer to
symptom 4 "One of the following
safety devices is activated" on
page 19. Refer to the explanation of
the digital controller in the chapter
"Resetting alarms" on page 13.
The unit is in anti-freeze alarm. Check on the controller and refer to
symptom 4 "One of the following
safety devices is activated" on
page 19. Refer to the explanation of
the digital controller in the chapter
"Resetting alarms" on page 13.
The remote ON/OFF input is
enabled and the remote switch is off.
Put the remote switch on or disable
the remote ON/OFF input.
The keyboard is locked. The user
parameter h09 is set to 0.
Unlock the controller keyboard.
Symptom 4.1: Overcurrent relay of compressor
POSSIBLE CAUSES CORRECTIVE ACTION
Failure of one of the phases. Check fuses on the supply panel or
measure the supply voltage.
Voltage too low. Measure the supply voltage.
Overload of motor. Reset. If the failure persists, call your
local dealer.
RESET Push the red button on the over-
current relay inside the switch box.
The controller still needs to be reset.
Symptom 4.2: Low pressure switch or anti-freeze alarm
POSSIBLE CAUSES CORRECTIVE ACTION
Water flow to water heat exchanger
too low.
Increase the water flow.
Shortage of refrigerant. Check for leaks and refill refrigerant,
if necessary.
Unit is working out of its operation
range.
Check the operation conditions of
the unit.
Inlet temperature to the water heat
exchanger is too low.
Increase the inlet water temperature.
Flow switch is not working or no
water flow.
Check the flow switch and the water
pump.
RESET After pressure rise, the low pressure
switch resets automatically, but the
controller still needs to be reset.
Symptom 4.3: High-pressure switch
POSSIBLE CAUSES CORRECTIVE ACTION
Condenser fan does not operate
properly in cooling mode.
Check that the fans turn freely. Clean
if necessary.
Water flow through water heat
exchanger is too low in heating
mode.
Increase the water flow.
Dirty or partially blocked condenser. Remove any obstacle and clean
condenser coil using brush and
blower.
Inlet air temperature of the
condenser is too high.
The air temperature measured at the
inlet of the condenser may not
exceed 43°C.
Outlet water temperature of the
condenser in heating mode is too
high.
The water temperature measured at
the outlet of the condenser may not
exceed 25°C.
RESET After pressure decrease, the high
pressure switch resets automatically,
but the controller still needs to be
reset.
Symptom 4.4: Fan thermal protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Mechanical failure (fan is blocked). Check that the fan rotates freely.
Air flow in the unit too low or outdoor
temperature too high.
Clean the air heat exchanger
properly.
RESET After temperature decrease, the
thermal protector is reset
automatically.
If the protector is activated
frequently, replace the motor or call
your local dealer.
Symptom 4.5: Reverse phase protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Two phases of the power supply are
connected in the wrong phase
position.
Invert two phases of the power
supply (by licensed electrician).
One phase is not connected
properly.
Check the connection of all phases.
RESET After inverting two phases or fixing
the power supply cables properly,
the protector is reset automatically,
but the controller still needs to be
reset.