5 | Operation
User reference guide
31
ETVH/X12S(U)18+23E + ETBH/X12E
Daikin Altherma 3 H MT F+W
4P634888-1A – 2022.08
2 Adjust the desired leaving water temperature.
+
35°C
2
a b
Main zone
+
45°C
3
a b
Additional zone
a Actual leaving water temperature
b Desired leaving water temperature
If scheduling is on after changing the desired leaving water temperature
The temperature will stay the same as long as there is no scheduled action.
The desired leaving water temperature will return to its scheduled value
whenever a scheduled action occurs.
You can avoid scheduled behaviour by (temporarily) turning off scheduling.
To turn off leaving water temperature scheduling
1 Go to one of the following:
[2.1]: Main zone > Schedule
[3.1]: Additional zone > Schedule
2 Select No.
To enable weather-dependent operation for the leaving water temperature
See "5.9.4Using weather-dependent curves"[448].
5.7 Domestic hot water control
5.7.1 About domestic hot water control
Depending on the DHW tank mode (installer setting), you use a different domestic
hot water control:
Reheat only
Schedule + reheat
Schedule only
CAUTION
The booster heater permission schedule is used to restrict or allow booster heater
operation based on a weekly program. Advice: In order to avoid unsuccessful
disinfection function, at least allow the booster heater (by the weekly program) for
minimum 4hours starting from the scheduled start-up of disinfection. If the booster
heater is restricted during disinfection, this function will NOT be successful and the
applicable warning AH will be generated.