5 | Application guidelines
Installer reference guide
43
EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01
b
c
d
c
A
B
a
b
e
A Main leaving water temperature zone
B One single room
a Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat)
b Non-return valve (field supply)
c Shut-off valve (field supply)
d Auxiliary boiler (field supply)
e Aquastat valve (field supply)
NOTICE
▪ Make sure the auxiliary boiler and its integration in the system complies with
applicable legislation.
▪ Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler
system.
▪ Make sure the return water to the heatpump does NOT exceed 60°C. To do so:
- Set the desired water temperature via the auxiliary boiler controller to
maximum 60°C.
- Install an aquastat valve in the return water flow of the heat pump. Set the
aquastat valve to close above 60°C and to open below 60°C.
▪ Install non-return valves.
▪ Make sure to only have one expansion vessel in the water circuit. An expansion
vessel is already pre-mounted in the indoor unit.
▪ Install the digital I/O PCB (option EKRP1HBAA).
▪ Connect X1 and X2 (changeover to external heat source) on the digital I/O PCB to
the auxiliary boiler. See "8.3.8 To connect the changeover to external heat
source"[4115].
▪ To setup the heat emitters, see "5.2 Setting up the space heating/cooling
system"[429].
Configuration
Via the user interface (configuration wizard):
▪ Set the use of a bivalent system as external heat source.
▪ Set the bivalent temperature and hysteresis.