5 | Application guidelines
Installer reference guide
33
EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01
Setting Value
Number of water temperature zones:
#: [4.4]
Code: [7-02]
0 (Single zone): Main
External room thermostat for the main
zone:
#: [2.A]
Code: [C-05]
1 (1 contact): When the used
external room thermostat or heatpump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Benefits
Cooling. The heat pump convector offers, besides heating capacity, also excellent
cooling capacity.
Efficiency. Optimal energy efficiency because of the interlink function.
Stylish.
Combination: Underfloor heating + Heatpump convectors
Space heating is provided by:
- The underfloor heating
- The heatpump convectors
Space cooling is provided by the heat pump convectors only. The underfloor
heating is shut off by the shut-off valve.
Setup
A
M1
B
a
A Main leaving water temperature zone
B One single room
a Heatpump convectors (+ controllers)
For more information about connecting the electrical wiring to the unit, see:
- "8.2Connections to the outdoor unit"[494]
- "8.3Connections to the indoor unit"[4101]
The heat pump convectors are connected as follows:
- Warm water → Indoor unit
- Cold water → Outdoor unit
A shut-off valve (field supply) is installed before the underfloor heating to
prevent condensation on the floor during cooling operation.