Daikin ETBX16DF9W handleiding
Handleiding
Je bekijkt pagina 102 van 264

8 | Electrical installation
Installer reference guide
102
EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01
Item Description
Heat pump convector There are different controllers and setups
possible for the heat pump convectors.
Depending on the setup, you also need
option EKRELAY1.
For more information, see:
▪ Installation manual of the heat pump
convectors
▪ Installation manual of the heat pump
convector options
▪ Addendum book for optional equipment
Wires: 0.75mm²
Maximum running current: 100mA
For the main zone:
▪ [2.9] Control
▪ [2.A] Thermostat type
For the additional zone:
▪ [3.A] Thermostat type
▪ [3.9] (read-only) Control
Remote outdoor sensor See:
▪ Installation manual of the remote outdoor
sensor
▪ Addendum book for optional equipment
Wires: 2×0.75mm²
[9.B.1]=1 (External sensor = Outdoor)
[9.B.2] Ext. amb. sensor offset
[9.B.3] Averaging time
Remote indoor sensor See:
▪ Installation manual of the remote indoor
sensor
▪ Addendum book for optional equipment
Wires: 2×0.75mm²
[9.B.1]=2 (External sensor = Room)
[1.7] Room sensor offset