8 | Electrical installation
Installer reference guide
114
EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01
CB
X2M
X2M
A4P
A4P
a
7 9
Y1YC
X1M
a Installation of EKRP1HBAA is required.
3 Fix the cable with cable ties to the cable tie mountings.
8.3.7 To connect the space cooling/heating ON/OFF output
INFORMATION
Cooling is only applicable in case of:
Reversible models
Heating only models + conversion kit (EKHBCONV)
Wires: (2+1)×0.75mm²
Maximum load: 0.3A, 250VAC
1 Open the following (see "6.2.5To open the indoor unit"[465]):
1 Front panel
1
2
3
2 Switch box cover
3 Switch box
2 Connect the space cooling/heating ON/OFF output cable to the appropriate
terminals as shown in the illustration below.
7
9
YCY2
X2M
12
3
A4P
1+2 Wires connected to the alarm output
3 Wire between X2M and A4P
A4P Installation of EKRP1HBAA is
required.