16 Charging refrigerant
Installation and operation manual
30
ERA200~300AMYFB
Inverter outdoor unit for AHU option kit and air curtains
4P780153-1 – 2024.07
▪ Use heat resistant polyethylene foam which can withstand a
temperature of 70°C for liquid piping and polyethylene foam which
can withstand a temperature of 120°C for gas piping.
▪ Reinforce the insulation on the refrigerant piping according to the
installation environment.
Ambient
temperature
Humidity Minimum thickness
≤30°C 75% to 80% RH 15mm
>30°C ≥80% RH 20mm
Between outdoor and indoor unit
1 Insulate and fix the refrigerant piping and cables as follows:
g
b
a
f
e
cd
a Gas pipe
b Gas pipe insulation
c Interconnection cable
d Field wiring (if applicable)
e Liquid pipe
f Liquid pipe insulation
g Finishing tape
2 Install the service cover.
Inside the outdoor unit
To insulate the refrigerant piping, proceed as follows:
a
b
a Insulation material
b Caulking etc.
1 Insulate the liquid and gas piping.
2 Wind heat insulation around the curves, and then cover it with
vinyl tape.
3 Make sure the field piping does not touch any compressor
components.
4 Seal the insulation ends (sealant etc.) (b, see above).
5 Where necessary, wrap the field piping with vinyl tape to protect
the insulation against sharp edges.
6 If the outdoor unit is installed above the indoor unit, cover the
stop valves with sealing material to prevent condensed water
on the stop valves from moving to the indoor unit.
NOTICE
Any exposed piping can cause condensation.
7 Reattach the service cover and the piping intake plate.
8 Seal all gaps to prevent snow and small animals from entering
the system.
a
a Seal
WARNING
Provide adequate measures to prevent that the unit can be
used as a shelter by small animals. Small animals that
make contact with electrical parts can cause malfunctions,
smoke or fire.
NOTICE
Do not block the air vents. This could affect air circulation
inside the unit.
15.3.5 To check for leaks after charging
refrigerant
After charging refrigerant in the system an additional leak test must
be performed. Refer to "16.6 To check refrigerant piping joints for
leaks after charging refrigerant"[432].
16 Charging refrigerant
16.1 Precautions when charging
refrigerant
WARNING
▪ Only use R32 as refrigerant. Other substances may
cause explosions and accidents.
▪ R32 contains fluorinated greenhouse gases. Its global
warming potential (GWP) value is 675. Do NOT vent
these gases into the atmosphere.
▪ When charging refrigerant, ALWAYS use protective
gloves and safety glasses.
NOTICE
If the power of some units is turned off, the charging
procedure cannot be finished properly.
NOTICE
Turn ON the power 6 hours before operation in order to
have power running to the crankcase heater and to protect
the compressor.
NOTICE
If operation is performed within 12 minutes after the indoor
and outdoor units are powered on, the compressor will not
operate before the communication is established in a
correct way between outdoor unit(s) and indoor units.
NOTICE
Before starting charging procedures, check if the
7‑segment display indication of the outdoor unit A1P PCB
is as normal (see "18.1.3To access mode 1 or 2"[4 37]).
If a malfunction code is present, see "22.1 Solving
problems based on error codes"[441].
NOTICE
Make sure all connected indoor units are recognised (see
setting [1‑10] in "18.1.6 Mode 1: monitoring
settings"[437]).