13 Special requirements for R32 units
Installation and operation manual
22
ERA200~300AMYFB
Inverter outdoor unit for AHU option kit and air curtains
4P780153-1 – 2024.07
Result: Total refrigerant charge limit for the system determined
using the graph for natural ventilation is 16.8kg.
Total amount of refrigerant in the system (7 kg) < Total refrigerant
charge limit (16.8 kg), which means that the Natural ventilation
safety measure can be applied.
0
5
10
14
20
25
35
45
55
40
30
50
5
6 8 10 12 14
97 11 13
m [kg]
A
min
[m
2
]
No safety measure
(c)
Alarm + natural ventilation
(f)
m Total refrigerant charge in the system [kg]
A
min
Minimum room area limit [m²]
(c) No safety measure (=No safety measure)
(f) Alarm + Natural ventilation (=Alarm + Natural ventilation)