Daikin ERA200AMYFB handleiding

48 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 7 van 48
2 Specific installer safety instructions
Installation and operation manual
7
ERA200~300AMYFB
Inverter outdoor unit for AHU option kit and air curtains
4P780153-1 – 2024.07
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
When connecting the power supply: connect the earth
cable first, before making the current-carrying
connections.
When disconnecting the power supply: disconnect the
current-carrying cables first, before separating the earth
connection.
The length of the conductors between the power supply
stress relief and the terminal block itself MUST be as
such that the current-carrying wires are tautened before
the earth wire is in case the power supply is pulled
loose from the stress relief.
Commissioning (see "19Commissioning"[438])
WARNING
Commissioning MUST be in accordance with the
instructions from this manual. See
"19Commissioning"[438].
CAUTION
Do NOT perform the test operation while working on
the indoor unit(s).
When performing the test operation, NOT ONLY the
outdoor unit, but the connected indoor unit will operate as
well. Working on an indoor unit while performing a test
operation is dangerous.
CAUTION
Do NOT insert fingers, rods or other objects into the air
inlet or outlet. Do NOT remove the fan guard. When the
fan is rotating at high speed, it will cause injury.
Troubleshooting (see "22Troubleshooting"[441])
WARNING
When carrying out an inspection on the switch box of
the unit, ALWAYS make sure that the unit is
disconnected from the mains. Turn off the respective
circuit breaker.
When a safety device was activated, stop the unit and
find out why the safety device was activated before
resetting it. NEVER shunt safety devices or change
their values to a value other than the factory default
setting. If you are unable to find the cause of the
problem, call your dealer.
WARNING
Prevent hazards due to inadvertent resetting of the thermal
cut-out: power to this appliance MUST NOT be supplied
through an external switching device, such as a timer, or
connected to a circuit that is regularly turned ON and OFF
by the utility.
2.1 Instructions for equipment using
R32 refrigerant
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
Do NOT pierce or burn refrigerant cycle parts.
Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
Be aware that the refrigerant inside the system is
odourless.
WARNING
The appliance shall be stored as follows:
in such a way as to prevent mechanical damage.
in a well-ventilated room without continuously operating
ignition sources (example: open flames, an operating
gas appliance or an operating electric heater).
in a room with dimensions as specified in "13 Special
requirements for R32 units"[417].
WARNING
Make sure installation, servicing, maintenance and repair
comply with instructions from Daikin and with applicable
legislation (for example national gas regulation) and are
executed ONLY by authorised persons.
WARNING
Take precautions to avoid excessive vibration or
pulsation to refrigeration piping.
Protect the protection devices, piping and fittings as
much as possible against adverse environmental
effects.
ALWAYS support the piping at distances of 1 m and
2m from the indoor unit.
Provide space for expansion and contraction of long
runs of piping.
Design and install piping in refrigerating systems such
as to minimise the likelihood of hydraulic shock
damaging the system.
Mount the indoor equipment and pipes securely and
protect them to avoid accidental rupture of equipment
or pipes in case of events such as moving furniture or
reconstruction activities.
CAUTION
Do NOT use potential sources of ignition in searching for
or detection of refrigerant leaks.
NOTICE
Do NOT re-use joints and copper gaskets which have
been used already.
Joints made in the installation between parts of the
refrigerant system shall be accessible for maintenance
purposes.