18 Configuration
Installation and operation manual
36
ERA200~300AMYFB
Inverter outdoor unit for AHU option kit and air curtains
4P780153-1 – 2024.07
A6P
A6P
a
a
b
b
b
ERA200 ERA250+300
A6P Printed circuit board (cool/heat selector)
a Cable to cool/heat selector switch (KRC19-26A )
b Cable tie
3 Turn ON the DIP switch (DS1‑1). See "18.1.2 Field setting
components"[437] for more information on the DIP switch.
OFF
ON
1 2 3 4
DS1 DIP switch 1
17.7 To check the insulation resistance
of the compressor
NOTICE
If, after installation, refrigerant accumulates in the
compressor, the insulation resistance over the poles can
drop, but if it is at least 1MΩ, then the unit will not break
down.
Use a 500V mega-tester when measuring insulation.
Do NOT use a mega-tester for low voltage circuits.
1 Measure the insulation resistance over the poles.
If Then
≥1MΩ Insulation resistance is OK. This procedure is
finished.
<1MΩ Insulation resistance is not OK. Go to the next step.
2 Turn ON the power and leave it on for 6hours.
Result: The compressor will heat up and evaporate any
refrigerant in the compressor.
3 Measure the insulation resistance again.
18 Configuration
DANGER: RISK OF ELECTROCUTION
INFORMATION
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
18.1 Making field settings
18.1.1 About making field settings
To continue the configuration of the ERA system, it is required to
give some input to the PCB of the unit. This chapter will describe
how manual input is possible by operating the push buttons on the
PCB and reading the feedback from the 7‑segment displays.
Next to making field settings it is also possible to confirm the current
operation parameters of the unit.
Push buttons and DIP switches
Item Description
Push buttons By operating the push buttons it is possible to:
Perform special actions (refrigerant charge,
testrun, etc).
Perform field settings (demand operation,
low noise, etc).
DIP switches By operating the DIP switches it is possible to:
DS1 (1): COOL/HEAT selector (refer to the
manual of the cool/heat selector switch).
OFF=not installed=factory setting
DS1 (2~4): NOT USED. DO NOT CHANGE
THE FACTORY SETTING.
DS2 (1~4): NOT USED. DO NOT CHANGE
THE FACTORY SETTING.
See also:
"18.1.2Field setting components"[437]
Mode 1 and 2
Mode Description
Mode 1
(monitoring
settings)
Mode1 can be used to monitor the current
situation of the outdoor unit. Some field setting
contents can be monitored as well.
Mode 2
(field settings)
Mode2 is used to change the field settings of
the system. Consulting the current field setting
value and changing the current field setting
value is possible.
In general, normal operation can be resumed
without special intervention after changing field
settings.
Some field settings are used for special
operation (e.g., one time operation, recovery/
vacuuming setting, manual adding refrigerant
setting, etc.). In such a case, it is required to
abort the special operation before normal
operation can restart. It will be indicated in
below explanations.
See also:
"18.1.3To access mode 1 or 2"[437]
"18.1.4To use mode 1"[437]
"18.1.5To use mode 2"[437]
"18.1.6Mode 1: monitoring settings"[437]
"18.1.7Mode 2: field settings"[438]