4P642495-1 2020.10 Page 36 of 52
Holding register
VRV
Sky-air
HRV
Split
VRV hydrobox LT
& HT
Air curtains
ERQ control box
Heating
Applied
Leaving water set
point
Leaving water set point cooling and
heating
* Applied: for cooling negative
leaving water set point: depending if
function is integrated in unit
software.
-
-
-
-
O
-
-
O
O*
42401 (1-00)
42405 (1-01)
.. (step of 4)
42653 (4-15)
Bit
Description
Meaning
15..0
Heating
water Set
point
- 127,9 ..
127,9°C
(unity: 0,1°C)
16 bit signed integer equals the value multiplied by 10
(bit 15= sign)
Remark:
1. In case the requested value is out of the unit set
point range and/or the user interface set point range,
the set point is set to the minimum limit value or higher
limit value.
2. For the result please check for the value in the input
register.
Note: The BMS needs to copy input register value:
32801 (1-00)… bit 15..0 to this holding register.
42402 (1-00)
42406 (1-01)
.. (step of 4)
42654 (4-15)
15..0
Cooling
water Set
point
- 127,9 ..
127,9°C
(unity: 0,1°C)
16 bit signed integer equals the value multiplied by 10
(bit 15= sign)
Remark:
1. In case the requested value is out of the unit set point
range and/or the user interface set point range, the set
point is set to the minimum limit value or higher limit
value.
2. For the result please check for the value in the input
register.
Note: The BMS needs to copy input register value:
32802 (1-00)… bit 15..0 to this holding register