Daikin EKMBDXB7V1 handleiding
Handleiding
Je bekijkt pagina 27 van 56

4P642495-1– 2020.10 Page 26 of 52
3
Normal
operation
0: Off
1: On (normal)
0: On (error)
2
Forced off
status
0: none
1: Forced off
or Indoor status of “Forced off” of digital input T1-T2
or by central “Forced off” by Modbus Interface DIII
1
-
0
On/off
status
0: Off
1: On
Input register
VRV
Sky-air
HRV
Split
VRV hydrobox LT
& HT
Air curtains
ERQ control box
Heating
Applied
Cooling/ Heating
Operation setting
mode
Depending on indoor unit capability
(fan only/Cool/heat/auto/dry)
* for split: no fan only mode
* for VRV hydrobox LT&HT & heating
& applied:
Only Heating&Cooling
* for HRV: Only ventilation
O
O
O*
O*
O*
O
O
O*
O*
Filter sign
Filter sign of indoor units
* Air curtain:
CYV models: not available
CYQ models: available
O
O
O
-
-
O*
-
O
-
Indoor status
Defrost/hot start status
Operation status
O
O
-
O
O
O
O
O
O
Cool/heat master
O
O
-
-
O
O
O
O
O
32002 (1-00)
32008 (1-01)
.. .. (step of 6)
32380 (4-15)
Bit
Description
Meaning
15
Cool/heat
master
0 till 2
0: not decided
1: Slave
2: Master (means possible to change cool/heat
operation mode via this indoor unit)
14
13
Defrost/ hot
start status
0: Off
1: On
12
-
11
Operation
status
0 till 2
0: Fan, 1: Heating, 2: Cooling
Actual running status.
10
9
8
7
Filter sign
status
0: Off
1 till 15: On
6
5
4
3
Operation
mode setting
0 till 7
0: Fan, 1: Heating, 2: Cooling, 3: Auto
4:Ventilation,5:-,6:-,7: Dry
2
1
0
Bekijk gratis de handleiding van Daikin EKMBDXB7V1, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.