4P642495-1– 2020.10 Page 20 of 52
2.3.3 Other DIII devices exist in the same system
(See 1.5 Overview of compatibilty with other DIII centralised control equipment)
No priority ranking is implemented. Meaning in case another DIII device is detected, the lock button & force
OFF functions are not available.
Detect other DIII
device
Return: No
Check Other DIII device exists (30001)
BMS
Modbus Interface DIII
Other DIII device (e.g.
iTM)
Power on
Power on
Other DIII device exists (30001
bit 1): No
(Forced OFF functions & lock
functions available)
Return: Yes
Check Other DIII device exists (30001)
Other DIII device exists (30001
bit 1): Yes
(Forced OFF functions & lock
functions not available)
BMS can use
Forced OFF
functions and lock
functions
BMS cannot use
Forced OFF
functions and lock
functions