Daikin EKEXVA300 handleiding
Handleiding
Je bekijkt pagina 20 van 36

13 Unit installation
Installation and operation manual
20
EKEACBVE + EKEXVA50~500
Option kit for combination of Daikin outdoor units with field-
supplied air handling units
4P724517-1 – 2023.06
≥50
≥100
≥400
≥100
≥400
≥50400
300
(mm)
≥200≥200
≥600≥600
(mm)
≥100≥100
≥200≥200
49150 1010
13.1.2 To install the control box
1 Open the cover with the key (delivered as accessory).
2 Attach the hanger brackets with their screws (delivered as
accessory) to the control box.
3 Fix the control box with its hanger brackets to the mounting
surface.
Use 4 screws (for holes of Ø6mm).
324
360
4× Ø6
(mm)
4×
4 For electrical wiring: see "15.1.1To connect the electrical wiring
to the control box"[423].
5 Close and lock the cover after installation to ensure that the
control box is watertight.
13.2 Expansion valve kit
13.2.1 Installation site requirements of the
expansion valve kit
Mind the following spacing installation guidelines:
≥250≥250
≥100≥100
(mm)
≥100≥150
≥600≥600
≥250≥250
≥100≥100
≥250≥250
≥100
≥100
≥250≥250
≥100
≥100
4978
215
401
13.2.2 To install the expansion valve kit
1 Make sure that the expansion valve kit is installed vertically.
2 Remove the cover by unscrewing 4× M5.
3 Drill 4 holes on the correct position (measurements as indicated
in figure below) and fix the expansion valve kit securely with 4
screws through the provided holes Ø9mm.
340
(mm)
192.5
4× Ø9
13.3 Thermistors
13.3.1 Location of the thermistors
Different thermistors need to be installed depending on the control
type. Follow the table below for this.
Thermistor Control type
X Y W Z Z'
R1T: Suction air — — — ● ●
R2T: Liquid pipe ● ● ● ● ●
R3T: Gas pipe ● ● ● ● ●
R4T: Discharge air — — — — ●
● Required
— Not required
Correct installation of the thermistors is required to ensure good
operation.
R1T Thermistor (suction air)
Install the thermistor either in the room that needs
temperature control or in the suction area of the air
handling unit.
Note: For room temperature control the delivered
thermistor (R1T) can be replaced by an optional remote
sensor kit (see the technical engineering data).
Bekijk gratis de handleiding van Daikin EKEXVA300, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Daikin |
Model | EKEXVA300 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 5715 MB |