0
2
4
6
8
10
12
14
16
m
c
[kg]
0 40 80 100 120
A
min_room
[m
2
]
16020 60 140
A
min_room
= (m
c
/ (2.5×(LFL)
(5/4)
×h
0
))
2
,
but not less than A
min_room
= m
c
/ (50%LFL×h
0
) (valid for m
c
>1.84 kg)
h
0
=1.8 m
h
0
=2.2 m
h
0
=2.5 m
1: Requirements for spaces served by AHU (m
c
≤16 kg)
Measures must be provided
following figures 2 and 3
No R32 safety requirements
2
4.9
4.0
3.5
2.5
6.1
5.0
4.4
3
8.6
6.0
5.3
3.5
11.6
7.8
6.1
4
15.2
10.2
7.9
4.5
19.2
12.9
10.0
5
23.7
15.9
12.3
5.5
28.7
19.2
14.9
6
34.1
22.8
17.7
6.5
40.0
26.8
20.8
7
46.4
31.1
24.1
7.5
53.2
35.7
27.6
8
60.6
40.6
31.4
8.5
68.4
45.8
35.5
9
76.6
51.3
39.8
9.5
85.4
57.2
44.3
10
94.6
63.4
49.1
10.5
104.3
69.8
54.1
11
114.5
76.6
59.4
11.5
125.1
83.8
64.9
12
136.2
91.2
70.6
12.5
147.8
99.0
76.6
13
159.9
107.0
82.9
13.5
172.4
115.4
89.4
14
185.4
124.1
96.1
14.5
198.9
133.1
103.1
15
212.8
142.5
110.4
15.5
227.2
152.1
117.8
16
242.1
162.1
125.5
m
c
[kg]
[m²] ] ]A
min_room
=1.8 m)(h
0
[m²A
min_room
=2.2 m)(h
0
[m²A
min_room
=2.5 m)(h
0
1