6 | Application guidelines
Installer reference guide
37
ERLA11~16D + EBSH/X(B)11+16P30+50D
Daikin Altherma 3 R ECH₂O
4P663482-1C – 2023.05
Heatpump convectors
Setup
B
a
A
A Main leaving water temperature zone
B One single room
a Heatpump convectors (+ controllers)
▪ For more information about connecting the electrical wiring to the unit, see:
- "9.2Connections to the outdoor unit"[4125]
- "9.3Connections to the indoor unit"[4129]
▪ The heatpump convectors are directly connected to the indoor unit.
▪ The desired room temperature is set via the controller of the heat pump
convectors. There are different controllers and setups possible for the heat pump
convectors. For more information, see:
- The installation manual of the heat pump convectors
- The installation manual of the heat pump convector options
- The addendum book for optional equipment
▪ The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X12M/15 and X12M/22).
▪ The space operation mode is sent to the heat pump convectors by one digital
output on the indoor unit (X12M/9 and X12M/10).
Configuration
Setting Value
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
Number of water temperature zones:
▪ #: [4.4]
▪ Code: [7-02]
0 (Single zone): Main
External room thermostat for the main
zone:
▪ #: [2.A]
▪ Code: [C-05]
1 (1 contact): When the used
external room thermostat or heatpump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.