Daikin EBSX11P50DG handleiding

316 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 19 van 316
3 | Specific installer safety instructions
Installer reference guide
19
ERLA11~16D + EBSH/X(B)11+16P30+50D
Daikin Altherma 3 R ECH₂O
4P663482-1C – 2023.05
Electrical installation (see
"9Electrical installation"[
4
121]
)
WARNING
Electrical wiring connection method MUST be in accordance with the instructions
from:
This manual. See "9Electrical installation"[4121].
The wiring diagram of the outdoor unit, which is delivered with the unit, located
at the inside of the service cover. For a translation of its legend, see "17.4Wiring
diagram: Outdoor unit"[4292].
The wiring diagram of the indoor unit, which is delivered with the unit, located on
the inside of the indoor unit switch box cover. For a translation of its legend, see
"17.5Wiring diagram: Indoor unit"[4293].
INFORMATION
Details of type and rating of fuses, or rating of circuit breakers are described in
"9Electrical installation"[4121].
DANGER: RISK OF ELECTROCUTION
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable national wiring regulation.
Make electrical connections to the fixed wiring.
All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.
Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
WARNING
Rotating fan. Before powering ON the outdoor unit, make sure that the discharge
grille covers the fan as protection against a rotating fan. See "7.3.6 To install the
discharge grille"[489].

Bekijk gratis de handleiding van Daikin EBSX11P50DG, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelEBSX11P50DG
CategorieNiet gecategoriseerd
TaalNederlands
Grootte49782 MB