Bind the power supply wire for
indoor PCB with the remote
controller wiring and the connection
wiring using clamp material.
1P224646-1A
CAUTION
Follow the “FIELD SETTING” in the installation manual of the remote controller for the indoor unit and make a necessary field setting in the remote controller after turning the air conditioner ON.
Set the remote controller to field set mode, select Mode No. “12”, and set the FIRST CODE NO. to “1” and the SECOND CODE NO. to “04”.
(The SECOND CODE NO. is factory set to “01”.)
Note: The remote control terminals (T1 and T2) of the indoor unit is for multi-tenant use. Therefore, the COMPUTERIZED CONTROL of the indoor unit is not available.
For connection to the terminal block, be sure to use a ring type crimp style terminal.
Also insulate the crimping portion, for example, by mounting an insulation sleeve.
For wiring, use the specified wire to connect it securely and fix it so that external force is not applied to the
terminal.
For tightening the terminal screw, use a proper screwdriver.
A smaller size screwdriver may damage the screw head, resulting in improper tightening.
If the terminal screw is secured too tightly, the screw may be damaged.
For tightening torque for terminal screw, see the table on the right-hand side.
Ring type crimp style terminal
Wire
Insulation sleeve
Terminal block of adaptor for multi tenant (X1M, X2M) 1.18~1.44
Tightening torque (N · m)
In the case of mounting to lid
of installation box for adaptor
*Processing procedure for field wiring
Adaptor power supply wire
through relay contact
(24VAC) (*field wiring)
Short-circuited
with electric wire.
Shall be clamped at
sheath portion.
Lid of installation box for adaptor
Adaptor for multi tenant
Power supply
wire for indoor
PCB (accessory)
Shall be clamped
near wiring stop.
In the case of mounting to
installation box for adaptor
Installation box for adaptor
Shall be clamped at
sheath portion.
Power supply
wire for indoor
PCB (accessory)
Shall be clamped
near wiring stop.
Adaptor power supply
wire through relay
contact (24VAC)
(*field wiring)
Adaptor for multi tenant
Short-circuited
with electric wire.
Power supply wire for adaptor (24VAC),
indoor contact input wire
Drain pump
lead wire
Installation box for adaptor
Power supply wire for indoor
PCB
Float switch lead wire
Bind the adaptor power supply wire (24VAC) and the indoor connection input
wire together with the drain pump lead wire using clamp material.
Be careful about jam at the lid
of electric component box.
Field wiring
Bind the provided power supply
wire for indoor PCB and the field
wiring using clamp material.
Bind the power supply wire for indoor
PCB with the float switch lead wire using
clamp material.
Power supply wire for BS
PCB (accessory)
Carry out wiring to keep it from
contact with electronic parts.
Bind using clamp material.
Adaptor for multi tenant
Adaptor power supply wire through
relay contact
(24VAC) (*field wiring)
(Do not take it for the 200-240VAC wire.)
Power supply wire for BS unit
Clamp it at the sheath portion
with the power supply wire for
BS unit.
FXMQ (Ceiling-mounted Duct Type)
FXFQ (Ceiling-mounted Cassette Round-flow Type)
BSVQ (BS unit)
*Processing procedure for field wiring
In the case of mounting to
installation box for adaptor (left)
In the case of mounting to
installation box for adaptor (right)
Short-circuited
with electric wire.
Short-circuited
with electric wire.
Adaptor power supply wire through relay contact
(24VAC) (*field wiring)
Adaptor power supply wire
through relay contact
(24VAC) (*field wiring)
Adaptor for multi
tenant
Power supply
wire for indoor
PCB (accessory)
Installation box for adaptor
Bind using clamp material.
Bind using clamp material.
Carry out wiring to keep it
from contact with parts on
the PCB.
Carry out wiring to keep it
from contact with parts on
the PCB.
Installation box for adaptor
Bind using clamp material.
Power supply wire for indoor
PCB (accessory)
Carry out field wiring to
keep it from contact with
parts on the PCB.
*Processing procedure for field wiring
*Processing procedure for field wiring
FXAQ (Wall-mounted type)
Power supply wire for indoor
PCB (accessory)
Adaptor for multi tenant
Power supply wire for indoor
PCB (accessory)
Adaptor power supply wire through relay contact
(24VAC) (*field wiring)
Short-circuited
with electric wire.
50 10 mm
+
50 10 mm
+
60 10 mm
+
50 10 mm
+
Bind using clamp material.
METHOD OF WIRING
5
FIELD SETTING
6
Short-circuited
with electric wire.