User’s Manual EM11A015H
intelligent Touch Manager
166
Example:
Time sequence Air conditioner 1 Air conditioner 2 Air conditioner 3
1 Valid Valid Invalid
2 Valid Valid “Unxed”
Target (input management point)
The interlock control may not be executed when the value is out of range within the required
duration.
Condition cleared immediately after program setup
If the input changes while the program is being edited or when toggling from disabled to enabled,
a condition may be considered cleared depending on the timing. Do not change settings when
input is about to change.
Simultaneous status change effects
In the event where input conditions becomes true for output 1 and output 2 simultaneously and
the target of both outputs is the same with opposite On and Off the function may temporarily
show unexpected behavior.
Example:
When the program is set as follows.
Input: 1-00, 1-01 Output 1: One input status change 1-02 turns ON
Output 2: All inputs status change 1-02 turns OFF
Required duration: 0 min
Output 1 and Output 2 conditions are
true simultaneously.
1-00 Operating
On
Stopped
Off
1-01 Operating
On
Stopped
Off
1-02 Operating
On
Stopped
Off
When 1-02 ON or 1-02 OFF is detected on controller
(Output 1: One condition is true), 1-02 may transiently
output ON signal.