User’s Manual EM11A015H
intelligent Touch Manager
14
1-2 System Conguration
DCM601A51
iTM
iTM
plus adaptor
iTM
plus adaptor
iTM
plus adaptor
iTM
plus adaptor
iTM
plus adaptor
iTM
plus adaptor
USB memory
Wireless modem
or
Di/Pi port
RS485
(Expansion adapter port)
Maximum number of nodes 30 nodes
External Management Points
RS485
Di/Pi port
Up to 7
DIII-NET port
Up to 64 groups
LAN port
USB port
DIII-NET port
ROUTER
Web Remote
Management
Port 1- 4:
Port 1:
Port 2- 4:
HUB/SWITCH/ROUTER/....
Emergency Stop signal input
Pulse input
Contact signal input
Emergency Stop signal input
Pulse input
Contact signal input
Intranet/Internet *4
Web Remote Management
possible from network
connected PC.
Maximum number of
registered users: 64
(Maximum 4 managers and
16 users can log in at the
same time)
Web Remote
Management
3
rd
party BACnet Server
Pump Light Fan Sensor
BACnet/IP
Chiller
Maximum
number of
50 servers
*1
*3
*2
*1 Cautions when monitoring/operating a Chiller management point
A Chiller management point can read and write the specic objects on a MicroTech III controller (POL687.70/MCQ) which is
embedded in a Chiller via BACnet/IP connection.
On that basis, the total operation of a Chiller unit (or a Chiller plant interlocking pumps and others) from intelligent Touch
Manager should be ensured by mechanical the installers and control engineering rms.
*2 Cautions when monitoring/operating a D3Chiller management point
The total operation of a D3Chiller unit (or a D3Chiller plant interlocking pumps and others) from intelligent Touch Manager
should be ensured by mechanical the installers and control engineering rms.
*3 Cautions when monitoring/operating an AHU management point
An AHU management point can read and write the specic objects on a MicroTech III controller (POL638.70/STD) which is
embedded in an AHU via BACnet/IP connection.
On that basis, the total operation of an AHU from intelligent Touch Manager should be ensured by mechanical the installers
and control engineering rms.
*4 If connecting to the Internet, connection must always be via a VPN router, and security must be ensured by the customer.