Daikin DCM008A51 handleiding
Handleiding
Je bekijkt pagina 121 van 369

User’s Manual EM11A015H
intelligent Touch Manager
120
4. If the outdoor temperature decreases, the setpoint is lowered up to 20°C by the Sliding
Temperature function.
When the room temperature further decreases to 16°C, this function changes the
operation mode to Heat. At that time, the setpoint becomes 16°C. At the beginning,
heating was started with setpoint at 20°C, however, the setpoint became 16°C as a result
of the change heat
→
cool
→
heat.
2. When this function is simultaneously used with the schedule and interlocking control functions,
this function may not work as intended with the settings.
Example: When the method for referencing room temperature and setpoint is set up to Fixed and
the thermal difference to 4°C.
1. Heating starts with setpoint for the indoor unit reference of indoor temperature and
setpoint set at 20°C.
2. The operation mode of that indoor unit is changed to Cool using the remote controller.
3. When the room temperature becomes 20°C or higher, the operation mode of the indoor
unit of the Auto Changeover group is changed to Cool and the setpoint set to 20°C. If the
operation mode had not been changed using the remote controller, the indoor unit works
in Heat mode until the room temperature becomes 24°C, and the setpoint should have
changed to 24°C when the operation mode changed to Cool but it didn’t.
Bekijk gratis de handleiding van Daikin DCM008A51, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Daikin |
| Model | DCM008A51 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 42750 MB |







