User’s Manual EM11A015H
intelligent Touch Manager
50
(3) Setpoint
Sets up whether changing the management points’ setpoint from the remote controller will be
enabled or disabled.
Permitted: Enabled.
Prohibited: Disabled.
In the case of the system with Hydrobox, the storage water setpoint can be changed even when “Prohibited” is selected.
NOTE
• A/C Tab
Sets up the indoor unit and Chiller.
Change settings by selecting the relevant check boxes. The range of values and items you can
set up will depend on the selected equipment.
(1)
(2)
(3)
(4)
(7)
(5)
(8)
(6)
(1) Operation Mode
Changes the operation mode.
Select and set up a value from Fan, Cool, Heat, Dependent, Automatic, and Dry.
• Dependent means either Cool or Heat. This is because the operation mode follows the
Cool or Heat operation mode set up in the air conditioner with Changeover option.
• To select the Dry operation mode, you need to complete the initial setup. Some air
conditioner models do not provide the Dry function.
• Setting up “Dry” in an indoor unit with Changeover option does not change the operation
mode of indoor units without Changeover option that belong to the same Outdoor Unit
group and are operating in Cool or Dry mode.
NOTE