Cause (3)
A power failure occurred.
Checking method
Use the iTM’s Schedule function to check if “Start Up” remains after the scheduled date/time.
Measure
Commands cannot be sent to equipment during a power failure.
File output to a USB memory fails.
iTM provides multiple functions such as Backup and Setup Export for outputting files to a
connected USB memory.
Check the following items if le output to a USB memory fails.
Free space of the destination USB memory is not enough.
Check free space of the USB memory. (5 GB or more is recommended)
The destination USB memory is write protected.
Unlock the write protection before use.
For how to unlock, see the instruction manual or etc, of the USB memory used.
If the destination USB memory contains any le with the same name, take one of the following
measures.
Move the le contained in the USB memory to a computer.
Change the name of the le contained in the USB memory.
Delete the le contained in the USB memory. (Conrm that deleting the le does not cause a problem.)
The USB memory is not connected to iTM.
Connect the USB memory to iTM and output the le again.
The USB memory is disconnected during le output.
Do not disconnect the USB memory during le output.
Connect the USB memory to iTM and output the le again.
When using analog management points, be sure that the Displayed accuracy is the same on the
iTM as on the equipment.