User’s Manual EM11A015H
intelligent Touch Manager
310
An area unit lter sign is ON on the Standard View screen.
The lter sign does not go off even when the air conditioner lter has been cleaned and the
cleaning sign has been reset using remote controller.
The lter sign on the Standard View screen is designed to go off only when the cleaning signs
for all of the air conditioners in the area are reset.
Check for any air conditioner in the area with the cleaning sign ON apart from the cleaned air
conditioner.
Touching an operation button may not cause a response.
If there is no response when you touch an operation button, or if there is a response when you
touch an area that is not an operation button, please correct the touch panel.
(See “6-10 Calibrating the Touch Panel”)
The Setting button is not available for touch on the Standard View screen.
“Prohibit Manual Operation” may be set up for the selected management point.
If “Manual Disable” is displayed in the List View as shown in the gure below, “Prohibit Manual
Operation” is set up.
Some functions cannot be operated or monitored.
If the target device does not have the corresponding function, it cannot be operated or monitored.
Please check the target device and its settings.