User’s Manual EM11A015H
intelligent Touch Manager
220
(3) OK button
Closes the Capacity Control Setup screen to return to the Control Setup screen.
When the outdoor unit capacity control is enabled, this button is disabled and you can only check
the settings.
<Processing on error>
• Select options. The larger the cut-off level is, the more strict the power consumption limitation
should be.
The degree of the power consumption limitation
[high] 0% > 40% > 70% > 100% [low]
Right setting Wrong setting
Cut-off level 1 70% Cut-off level 1 0%
Cut-off level 2 40% Cut-off level 2 40%
Cut-off level 3 0% Cut-off level 3 70%
(4) Cancel button
Closes the Capacity Control Setup screen to return to the Control Setup screen.
(5) Capacity combo box (the text area is displayed when the outdoor unit capacity control is
enabled.)
Displays the value of the outdoor unit capacity for the cut-off level 1 to 3.
The default value is 100% for all the levels.
When the outdoor unit capacity control is enabled, the text area is displayed and you cannot
change the value of the outdoor unit capacity.