User’s Manual EM11A015H
intelligent Touch Manager
218
(3) OK button
Closes the Setting Temperature Control Setup screen to return to the Control Setup screen.
When the setting temperature control is enabled, this button is disabled and you can only check the
settings.
<Processing on error>
• Select options. The larger the cut-off level is, the more strict the power consumption limitation
should be.
The degree of the power consumption limitation
[high] Thermostat OFF > 16°C > 15°C …1°C > 0°C [low]
Right setting Wrong setting
Cut-off level 1 2.0°C Cut-off level 1 Thermostat OFF
Cut-off level 2 3.0°C Cut-off level 2 3.0°C
Cut-off level 3 Thermostat OFF Cut-off level 3 2.0°C
(4) Cancel button
Closes the Setting Temperature Control Setup screen to return to the Control Setup screen.
(5) Start Level combo box (the text area is displayed when the setting temperature control is
enabled.)
Sets the cut-off level that triggers the control.
When the setting temperature control is enabled, the text area is displayed and you cannot change
the start level.
The default is level 1.
(6) Cooling Setpoint Upper Limit text eld
When cooling, you can set the upper limit for the setpoint shifting for the demand control.
Touch the Modify button to display the numerical input dialog that allows you to change the cooling
setpoint upper limit. You can set the value in increments of 0.1°C.
When the setting temperature control is enabled, you cannot change the cooling setpoint upper
limit. (The Modify button is not displayed.)
The default value is 28.0°C.
(7) Heating Setpoint Lower Limit text eld
When heating, you can set the lower limit for the setpoint shifting for the demand control.
Touch the Modify button to display the numerical input dialog that allows you to change the heating
setpoint lower limit.
You can set the value in increments of 0.1°C.
When the setting temperature control is enabled, you cannot change the heating setpoint lower
limit. (The Modify button is not displayed.)
The default value is 18.0°C.