User’s Manual EM11A015H
intelligent Touch Manager
165
Interlocking Control Restrictions
Handling of communication error
The input condition is either a “valid” or “invalid” status of the target (input management point).
When a communication error occurs, the status is handled as “unfixed” because it cannot be
assessed.
Handling of start
The initial status of a target (input management point) when started is handled as “unxed”.
Handling of equipment error
When an equipment error occurs, if the detection target is anything but the “equipment error”, the
status of the management point is handled as “unxed”.
Handling of maintenance
If the management point of the detection target is being checked, the status of the management
point is handled as “unxed”.
This function does not work when the management point target of condition control is in
maintenance.
Handling of “unxed”
The changes in a status before and after “unxed” (“valid (invalid)
unxed” or “unxed
valid
(invalid)”) are not considered triggers of cleared conditions.
When returning from the status of “unxed”, the status before “unxed” remains until the change
in a status occurs.
Operation when the detection target includes “unxed”
When “unxed” is included in the status of the management point of the detection target, if all
management points excluding “unxed” become valid (invalid), its interlocking program may be
executed.
<When interlocking control is performed>
When one management point changes to valid (invalid), and all management points excluding
“unxed” become valid (invalid) accordingly, the interlocking program is executed.
Example:
Time sequence Air conditioner 1 Air conditioner 2 Air conditioner 3
1 Valid Invalid “Unxed”
2 Valid Valid “Unxed”
<When interlocking control is not performed>
When one management point changes to “unfixed”, and all management points excluding
“unxed” become valid (invalid) accordingly, the interlocking program is not executed.