User’s Manual EM11A015H
intelligent Touch Manager
161
3. Effect on Other Functions
Use of Switch as trigger Use of On/Off status for assessment
Central Monitoring
−
• Setback Active
⇒
Treated as ON
• Setback Inactive
⇒
Treated as OFF
Automatic
Control
Schedule
− −
Pre-Cool/Pre-
Heat
− −
Interlocking
• Start order by Setback
⇒
Treated as start trigger
• Stop order by Setback
⇒
Treated as stop trigger
−
Emergency
Stop
− −
Auto
Changeover
−
• Setback Active
⇒
Not treated as ON
• Setback Inactive
⇒
Treated as OFF
Temperature
Limit
−
• Setback Active
⇒
Treated as ON
• Setback Inactive
⇒
Not treated as OFF
Sliding
Temperature
− −
HMO
−
• Setback Active
⇒
Not treated as ON
• Setback Inactive
⇒
Treated as OFF
Timer
Extension
• Start order by Setback
⇒
Not treated as start trigger
• Stop order by Setback
⇒
Treated as stop trigger
• Setback Active
⇒
Not treated as ON
• Setback Inactive
⇒
Treated as OFF
Data
Management
Power
Proportional
Distribution
−
• Setback Active
⇒
Treated as ON
• Setback Inactive
⇒
Treated as OFF
Energy
Navigator
(Timer
Extension
sampling)
−
• Setback Active
⇒
Not treated as ON
• Setback Inactive
⇒
Treated as OFF
Operation
time trend
−
• Setback Active
⇒
Treated as ON
• Setback Inactive
⇒
Treated as OFF
Start/Stop
count trend
• Start order by Setback
⇒
Treated as start trigger
• Stop order by Setback
⇒
Treated as stop trigger
−