112
Cautions when Using Simultaneously with Other Control Functions
1. Start/Stop of air conditioners by the Heating Mode Optimization function does not affect the
operation of this function.
2. If the Pre-Cool/Pre-Heat function is simultaneously set up, the air conditioners may be stopped
before the time set up by this function, preventing the temperature to reach the setpoint at the
set time.
Example: 1. Duration is set to 30 minutes.
2. Pre-Cool/Pre-Heat is enabled to achieve 20°C at 9:00 by schedule.
3. The air conditioners are automatically started at 8:15 by the Pre-Cool/Pre-Heat
function.
4. This function stops the air conditioners at 8:45. Therefore, the air conditioners are
stopped by 9:00, the time set in the schedule.