Part 1: Operation Operation in normal mode
9
W Service (automatic reset after 15 min)
heat generator regulated to heat generator set temperature
= max. heat generator temperature= see page 35 ; when
the heat generator temperature has reached 65 °C, the
consumers are regulated to their flow temperature to dissi-
pate heat (cooling function).
! The cooling function must be explicitly enabled in
the consumer circuits by means of the parameter
B-HEAT SINK.
Effect of the operating mode
The operating mode set here affects the HS regulation and
the integrated heating circuits of the controller.
Each heating circuit can be assigned a separate operating
mode from the one set by means of the "operating mode"
parameter in the user level of the corresponding heating
circuit.
If the "i = Standby/OFF", and "F = Summer mode" oper-
ating modes are set at the boiler controller, these settings
have a reducing effect on all heating circuits / consumer
circuits that are present in the entire system.
! For mixing controller only on these heating circuits.