13 Unit installation
Installation and operation manual
23
BS4~12A14AJV1B9
VRV 5 branch selector unit
4P797565-1 – 2024.11
13.1 Preparing the installation site
WARNING
The appliance shall be stored/installed as follows:
in such a way as to prevent mechanical damage.
in a well-ventilated room without continuously operating
ignition sources (example: open flames, an operating
gas appliance or an operating electric heater).
in a room with dimensions as specified in "12 Special
requirements for R32 units"[413].
Avoid installation in an environment with a lot of organic solvents
such as ink and siloxane.
Do NOT install the unit in places often used as work place. In case
of construction works (e.g. grinding works) where a lot of dust is
created, the unit MUST be covered.
Choose an installation location with sufficient space to carry the unit
in and out of the site.
13.1.1 Installation site requirements of the unit
CAUTION
Appliance is NOT accessible to the general public. Install it
in a secured area, protected from easy access.
This unit is suitable for installation in a commercial and
light industrial environment.
CAUTION
This equipment is NOT intended for use in residential
locations and will NOT guarantee to provide adequate
protection to radio reception in such locations.
NOTICE
If the equipment is installed closer than 30 m to a
residential location, the professional installer MUST
evaluate the EMC situation before installation.
NOTICE
The installation and any maintenance requires a
professional with relevant EMC experience to install any
specific EMC mitigation measures defined in the user
instructions.
NOTICE
The equipment described in this manual may cause
electronic noise generated from radio-frequency energy.
The equipment complies to specifications that are
designed to provide reasonable protection against such
interference. However, there is no guarantee that
interference will NOT occur in a particular installation.
It is therefore recommended to install the equipment and
electric wires in such a way that they keep a proper
distance from stereo equipment, personal computers, etc.
In places with weak reception, keep distances of 3 m or
more to avoid electromagnetic interference of other
equipment and use conduit tubes for power and
interconnection lines.
INFORMATION
Equipment meets the requirement for commercial and
light-industrial location when professionally installed and
maintained.
INFORMATION
The sound pressure level is less than 70dBA.
INFORMATION
Also read the following requirements:
Service space requirements. See below in this topic.
Refrigerant piping requirements. See "14 Piping
installation"[430].
Safety measures differ depending on the total amount of refrigerant
in the system and on the floor area. See "12.3 To determine the
required safety measures"[413].
The BS unit is designed for indoor installation only. Always respect
the following conditions.
Ambient condition Value
Indoor temperature 5~32°CDB
Indoor humidity ≤80%
Do NOT install the unit in the following places:
In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall
off or cause water leakage.
Where acidic or alkaline vapour is present.
In vehicles or vessels.
It is NOT recommended to install the unit in the following places
because it may shorten the life of the unit:
In places where voltage fluctuates a lot.
Water leakage. Take care that in the event of a water leak, water
CANNOT cause any damage to the installation space and its
surroundings.
Noise. Choose a location where the operation noise of the unit
does not disturb the room occupants. To avoid that the refrigerant
noise disturbs the people in the room, keep at least 5m of piping
between the occupied room and the BS unit. If there is no false
ceiling in the room, it is advised to add sound insulation around
the piping between the BS unit and the indoor unit, or to keep
more length between the BS unit and the indoor unit.
>5 m
c
a
b
b
a
a BS unit
b Indoor unit
c Sound insulation (field supply)
Drainage. Make sure condensation water can be evacuated
properly.
Drain pipe length. Keep drain piping as short as possible.
Drain pipe size. Keep the pipe size equal to or greater than that
of the connecting pipe (vinyl pipe of 20mm nominal diameter and
26mm outer diameter).
Bad odours. To prevent bad odours and air going into the unit
through the drain piping, install a trap.