7 | Smart Grid application
Installer reference guide
41
BRP069A61+BRP069A62
Daikin Altherma LAN adapter
4P464229-1E – 2023.11
During space cooling operation:
- Outdoor temperature < space cooling setting [F-01]
INFORMATION
The system will ONLY buffer energy when the indoor unit is NOT in normal
operation. Normal operation has priority over energy buffering.
Normal operation CAN be any of the following: Space heating/cooling
(setpoint is not reached), Domestic hot water operation (setpoint is not
reached during a scheduled operation or a reheat operation), or safety functions
(e.g. Antifrost or Disinfection).
The maximum temperature during domestic hot water tank buffering is the
maximum tank temperature for the applicable tank type.
The space heating/cooling setpoint during room buffering is the buffering
setpoint for the room.
The system will ONLY buffer energy during space heating if the space heating
setpoint is lower than the space heating comfort setpoint. The system will ONLY
buffer energy during space cooling if the space cooling setpoint is higher than the
space cooling comfort setpoint.
INFORMATION
Tank/room buffering priority:
The system starts tank buffering first. When tank buffering is at its maximum
capacity, then the system switches to room buffering (if enabled).
Tank buffering can switch to room buffering prior to reaching the maximal
capacity because of internal unit logic. In normal operation, the maximum
running time for domestic hot water is applicable. See the installer reference
guide of the indoor unit for more details.
When room buffering is ongoing and the tank drops below its maximum capacity
(e.g. someone takes a shower), then the system stays at room buffering for a
certain amount of time before it switches back to tank buffering.
INFORMATION
Tank buffering:
When Reheat only or Reheat + scheduled is used, the boiler can use energy from
the grid until the setpoint is reached. If Schedule only is used, a cold boiler can be
the result if the schedule is NOT well set.
Due to the nature of the system, the tank CAN cool down in some cases because
of a too short reheat cycle.
INFORMATION
To avoid undesired grid consumption and frequent start/stops of the electrical
heater due to variations on the voltage tolerance of the grid, several
countermeasures were implemented. As a result, the electrical heater will not be
used for space heating, even if this is allowed via the user interface.
INFORMATION
Because of cloudy weather circumstances or sudden peaks in household
consumption, the excess PV power CAN fluctuate. To avoid frequent switching of the
unit operation, a timer is implemented so that buffering will ONLY stop when the
excess PV power drops below the threshold for at least 5 minutes. Due to this, the
unit CAN temporarily consume energy from the grid to continue buffering.