Daikin BRC1H51W handleiding
Handleiding
Je bekijkt pagina 22 van 32

13 Configuration
Installer and user reference guide
22
BRC1H51W+K+S
Wired remote controller
4P513689-1 – 2018.02
Parameter Description Possible values Default value
B2 Reset Timer Timer that starts from as soon the
Delay Timer expires. When this
timer expires, the previous state
(i.e. regular setpoint) changes to
the "Default Reset Setting" state.
0-20 hours "20 hours"
Reset ON/OFF "Default Reset Setting" on/off
state
"ON", "OFF", "--" "OFF"
Reset Mode "Default Reset Setting" operation
mode
Auto, Cooling, Heating, Fan only,
--
"--"
Reset Cool SP "Default Reset Setting" cooling
setpoint
See indoor unit's setpoint range
and setpoint range limitation, "--"
"22°C"
Reset Heat SP "Default Reset Setting" heating
setpoint
See indoor unit's setpoint range
and setpoint range limitation, "--"
"22°C"
INFORMATION
When the value for a parameter is "- -", this means that
when the timers expires, nothing changes for that
parameter and the current active value is kept.
Window contact logic
Window contact B1 Key card contact B2 Time Action
Contact closed (window open) Contact closed (key card IN) — ▪ Normal indoor unit operation.
▪ The unit returns to the previous
state before opening the
contact.
Contact open (window open) Contact closed (key card IN) — Unit operation is forced off:
▪ No delay and reset timer
functionality.
▪ Not possible to turn on/off the
unit with the controller's ON/OFF
button.
Bekijk gratis de handleiding van Daikin BRC1H51W, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Daikin |
| Model | BRC1H51W |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 3544 MB |







