Daikin BRC1H51W handleiding

32 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 17 van 32
13 Configuration
Installer and user reference guide
17
BRC1H51W+K+S
Wired remote controller
4P513689-1 – 2018.02
Indoor unit field settings
The setting procedure is different depending on whether you want to
make settings for individual units, or for grouped units.
Individual indoor units
Define a mode by setting a Mode number (number between
brackets)
Define the unit to which the setting will apply by setting a Unit
number
Define the setting by setting a SW number
Define a value for that setting
Grouped indoor units
Define a mode by setting a Mode number (number NOT between
brackets)
Do NOT set a Unit number (setting applies to all the units in the
group)
Define the setting by setting a SW number
Define a value for that setting
Mode SW Setting (SW) description
01 02 03 04
10 (20) 00 Filter contamination timer: set the timer for
the appearance of the "Time to clean filter"
sreen.
Ultra long life filter Light ±10000 hrs. Heavy ±5000 hrs
Long life filter ±2500 hrs ±1250 hrs
Standard filter ±200 hrs ±100 hrs
01 Long life filter: if applicable, set which type of long life filter is used. Long life filter Ultra long life filter
02 Controller thermostat sensor: set how the controller thermostat sensor
is used.
Used in combination with indoor
unit thermistor
Not used Used
exclusively
03 Disable filter sign: set whether or not the filter sign can be displayed. Display Do not display
11 (21) 00 Simultaneous operation: set the simultaneous indoor unit operation
mode (Sky Air)
Pair Twin Triple Double twin
12 (22) 01 External On/OFF input: set the operation of voltage free contacts T1/T2
(indoor unit contacts)
Forced OFF On/OFF operation Emergency Forced OFF
(multi-tenant)
02 Thermostat differential: if the system contains a remote sensor, set the
increase/decrease increments.
1°C 0.5°C
13 (23) 00 High air outlet velocity: set in case of high-ceiling applications. h≤2.7m 2.7m<h≤3m 3m<h≤3.5m
01 Airflow direction: set in case an indoor unit is equipped with an option
kit that blocks the airflow.
4-way flow 3-way flow 2-way flow
03 Airflow function: set whether the indoor unit is equipped with a
decoration panel at its air outlet.
Equipped Not equipped
04 Airflow direction range Upper Normal Lower
06 External static pressure: set the external static pressure (according to
the resistance of the connected ducts).
Normal High static pressure Low static
pressure
FHYK: follow the high-ceiling setting. Normal High ceiling
15 (25) 03 Humidification drain pump: set whether the system is equipped with a
humidification drain pump.
Equipped Not equipped
1c 01 Thermostat sensor: set which thermostat sensor you want to use. Indoor unit thermistor Controller thermistor
1c 12 Window contact B1 (external input) Do not use Use
1c 13 Key card contact B2 (external input) Do not use Use
1e 02 Setback function: set Setback operation. No Setback Heating only Cooling only Heating and
Cooling
1e 07 Rotation overlap time. Set the Rotation overlap time. 30 minutes 15 minutes 10 minutes 5 minutes
INFORMATION
The connection of optional accessories to the indoor
unit might cause changes to some field settings. For
more information, see the installation manual of the
optional accessory.
For details about the specific field settings of each type
of indoor unit, see the installation manual of the indoor
units.
Field settings that are not available for a connected
indoor unit are not displayed.
Field setting default values are different depending on
the indoor unit model. For more information, see the
service manual of the indoor units.

Bekijk gratis de handleiding van Daikin BRC1H51W, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelBRC1H51W
CategorieNiet gecategoriseerd
TaalNederlands
Grootte3544 MB