13 Configuration
Installer and user reference guide
17
BRC1H51W+K+S
Wired remote controller
4P513689-1 – 2018.02
Indoor unit field settings
The setting procedure is different depending on whether you want to
make settings for individual units, or for grouped units.
Individual indoor units
▪ Define a mode by setting a Mode number (number between
brackets)
▪ Define the unit to which the setting will apply by setting a Unit
number
▪ Define the setting by setting a SW number
▪ Define a value for that setting
Grouped indoor units
▪ Define a mode by setting a Mode number (number NOT between
brackets)
▪ Do NOT set a Unit number (setting applies to all the units in the
group)
▪ Define the setting by setting a SW number
▪ Define a value for that setting
Mode SW Setting (SW) description —
01 02 03 04
10 (20) 00 Filter contamination timer: set the timer for
the appearance of the "Time to clean filter"
sreen.
Ultra long life filter Light ±10000 hrs. Heavy ±5000 hrs — —
Long life filter ±2500 hrs ±1250 hrs
Standard filter ±200 hrs ±100 hrs
01 Long life filter: if applicable, set which type of long life filter is used. Long life filter Ultra long life filter — —
02 Controller thermostat sensor: set how the controller thermostat sensor
is used.
Used in combination with indoor
unit thermistor
Not used Used
exclusively
—
03 Disable filter sign: set whether or not the filter sign can be displayed. Display Do not display — —
11 (21) 00 Simultaneous operation: set the simultaneous indoor unit operation
mode (Sky Air)
Pair Twin Triple Double twin
12 (22) 01 External On/OFF input: set the operation of voltage free contacts T1/T2
(indoor unit contacts)
Forced OFF On/OFF operation Emergency Forced OFF
(multi-tenant)
02 Thermostat differential: if the system contains a remote sensor, set the
increase/decrease increments.
1°C 0.5°C — —
13 (23) 00 High air outlet velocity: set in case of high-ceiling applications. h≤2.7m 2.7m<h≤3m 3m<h≤3.5m
01 Airflow direction: set in case an indoor unit is equipped with an option
kit that blocks the airflow.
4-way flow 3-way flow 2-way flow —
03 Airflow function: set whether the indoor unit is equipped with a
decoration panel at its air outlet.
Equipped Not equipped
04 Airflow direction range Upper Normal Lower —
06 External static pressure: set the external static pressure (according to
the resistance of the connected ducts).
Normal High static pressure Low static
pressure
—
FHYK: follow the high-ceiling setting. Normal High ceiling — —
15 (25) 03 Humidification drain pump: set whether the system is equipped with a
humidification drain pump.
Equipped Not equipped — —
1c 01 Thermostat sensor: set which thermostat sensor you want to use. Indoor unit thermistor Controller thermistor — —
1c 12 Window contact B1 (external input) Do not use Use
1c 13 Key card contact B2 (external input) Do not use Use
1e 02 Setback function: set Setback operation. No Setback Heating only Cooling only Heating and
Cooling
1e 07 Rotation overlap time. Set the Rotation overlap time. 30 minutes 15 minutes 10 minutes 5 minutes
INFORMATION
▪ The connection of optional accessories to the indoor
unit might cause changes to some field settings. For
more information, see the installation manual of the
optional accessory.
▪ For details about the specific field settings of each type
of indoor unit, see the installation manual of the indoor
units.
▪ Field settings that are not available for a connected
indoor unit are not displayed.
▪ Field setting default values are different depending on
the indoor unit model. For more information, see the
service manual of the indoor units.