11 Starting up the system
Installer and user reference guide
11
BRC1H51W+K+S
Wired remote controller
4P513689-1 – 2018.02
10.5 Opening the controller
10.5.1 Precautions when opening the controller
NOTICE
The controller PCB is mounted into the front casing. When
opening the controller, be careful not to damage the PCB.
NOTICE
When the front and rear casing are separated, make sure
the PCB does not come into contact with dust or moisture.
10.5.2 To open the controller
1 Insert a flat‑head screwdriver into one of the bottom closing
mechanisms and slowly twist it.
11 Starting up the system
CAUTION
Before starting up the system, make sure:
The indoor and outdoor unit wiring is completed.
The switch box covers of the indoor and outdoor units
are closed.
INFORMATION
It is only possible to use a master and a slave controller of
the same type.
INFORMATION
In case digital input adapter BRP7A5* is part of the
system, it is not possible to connect and designate a
second controller. Connecting a second controller when
the system already contains the adapter, will cause the
adapter to go in error.
The controller gets its power from the indoor unit. It will start up as
soon as it is connected. For the controller to be operable, therefore
make sure the indoor unit is powered on.
Once the controller is powered, it will automatically start up. If it is
the first and only controller that is connected to the indoor unit, it will
automatically get designated as master controller. For a second
controller to get designated as slave controller, manual action is
required. For instructions, see "11.2 To designate a controller as
slave"on page11.
11.1 Master and slave controller
a
b
c d
a Outdoor unit
b Indoor unit
c Master remote controller
d Slave remote controller
11.2 To designate a controller as slave
Prerequisite: A master controller is already connected to the indoor
unit.
1 Connect a second controller.
Result: It will start up automatically.
2 Wait for a U5 or U8 error to appear on the screen.
3 When the U5 or U8 error appears, press and keep it
pressed until "2" appears on the screen.
Result: The controller is now designated as slave.
INFORMATION
If the slave controller does not display the home screen
two minutes after its designation, turn off the power and
check the wiring.
12 Operation
12.1 Buttons
+
-
c b d
e
a