16 | Technical data
Installer reference guide
74
AZAS100~140MUV/Y
Sky Air Active-series
4P743509-1B – 2024.05
Multiple rows of units ( )
b (mm)
≥1000
≥200
≥2000
≥100
≥3000
≥1500
b
≥100
≥100
≥100
≥100
≥250
≥250
H
B
H
U
H
B
≤½H
U
b≥250
½H
U
<H
B
≤H
U
b≥300
H
B
>H
U
H
B
H
U
Stacked units (max. 2 levels) ( )
A1
A2
≥500
≥1000
A2
≥500
≥300
≥100
≥100
B1
A2
B2
≥100
≥300
≥100
≥100
B2
≥100
≥1000
B2
A1=>A2 (A1) If there is danger of drainage dripping and freezing between the upper and
lower units…
(A2) Then install a roof between the upper and lower units. Install the upper unit
high enough above the lower unit to prevent ice buildup at the upper unit's bottom
plate.
B1=>B2 (B1) If there is no danger of drainage dripping and freezing between the upper and
lower units…
(B2) Then it is not required to install a roof, but seal the gap between the upper
and lower units to prevent discharged air from flowing back to the suction side
through the bottom of the unit.