15 Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of
the refrigerant, oil and other parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
In this chapter
15.1 Overview: Disposal ................................................................................................................................................................. 70
15.2 About pump down.................................................................................................................................................................. 70
15.3 To pump down........................................................................................................................................................................ 70
15.1 Overview: Disposal
Typical workflow
Disposing of the system typically consists of the following stages:
1 Pumping down the system.
2 Bringing the system to a specialized treatment facility.
INFORMATION
For more details, see the service manual.
15.2 About pump down
The unit is equipped with an automatic pump down function, with which you can
collect all refrigerant from the system into the outdoor unit.
NOTICE
The outdoor unit is equipped with a low pressure switch or a low pressure sensor to
protect the compressor by turning it OFF. NEVER short-circuit the low pressure
switch during pump down operation.
15.3 To pump down
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self-
combustion and explosion of the compressor because of air going into the
operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
1 Turn ON the main power supply switch.
2 Make sure the liquid stop valve and the gas stop valve are open.