11 | Commissioning
Installer reference guide
65
AZAS100~140MUV/Y
Sky Air Active-series
4P743509-1B – 2024.05
Error code Possible cause
E7 There is a missing phase in case of three-phase
power supply units.
Note: Operation will be impossible. Turn OFF the
power, recheck the wiring, and switch two of the
three electrical wires.
L4 The air inlet or air outlet is blocked.
U0 The stop valves are closed.
U2 ▪ There is a voltage imbalance.
▪ There  is  a  missing  phase  in  case  of  three-phase
power  supply  units.  Note:  Operation  will  be
impossible.  Turn  OFF  the  power,  recheck  the
wiring,  and  switch  two  of  the  three  electrical
wires.
U4 or UF The inter-unit branch wiring is not correct.
UA The outdoor and indoor unit are incompatible.
NOTICE
▪ The reversed phase protection detector of this product only functions when the
product  starts  up.  Consequently  reversed  phase  detection  is  not  performed
during normal operation of the product.
▪ The  reversed  phase  protection  detector  is  designed  to  stop  the  product  in  the
event of an abnormality when the product is started up.
▪ Replace  2  of  the  3  phases  (L1,  L2,  and  L3)  during  reverse-phase  protection
abnormality.