6 | Unit installation
Installer reference guide
24
AZAS100~140MUV/Y
Sky Air Active-series
4P743509-1B – 2024.05
NOTICE
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies with specifications that are
designed to provide reasonable protection against such interference. However, there
is no guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires in such a
way that they keep a proper distance from stereo equipment, personal computers,
etc.
b
a
c
df e
(mm)
≥
1500
≥
1500
≥
1000
≥
1000
≥
1000
≥
1000
a Earth leakage protector
b Fuse
c Outdoor unit
d Indoor unit
e User interface
f Personal computer or radio
▪ In places with weak reception, keep distances of 3 m or more to avoid
electromagnetic disturbance of other equipment and use conduit tubes for
power and transmission lines.
▪ Select a place where rain can be avoided as much as possible.
▪ Ensure that in the event of a water leak, no damage occurs to the installation
space or its surroundings.
▪ Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone and the location is selected according the
applicable legislation.
▪ Heat exchanger fins are sharp and injury is possible. Choose an installation
location where there is no risk for injury (especially in areas where children play).
Do NOT install the unit in the following places:
▪ Sound sensitive areas (e.g. near a bedroom), so that the operation noise will
cause no trouble.
Note: If the sound is measured under actual installation conditions, the
measured value might be higher than the sound pressure level mentioned in
Sound spectrum in the data book due to environmental noise and sound
reflections.
INFORMATION
The sound pressure level is less than 70dBA.
▪ In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may
shorten the life of the unit:
▪ Where the voltage fluctuates a lot
▪ In vehicles or vessels
▪ Where acidic or alkaline vapour is present