6 | Unit installation
Installer reference guide
23
AZAS100~140MUV/Y
Sky Air Active-series
4P743509-1B – 2024.05
6 Unit installation
In this chapter
6.1 Preparing the installation site ................................................................................................................................................ 23
6.1.1 Installation site requirements of the outdoor unit ............................................................................................... 23
6.1.2 Additional installation site requirements of the outdoor unit in cold climates ................................................... 26
6.2 Opening and closing the unit ................................................................................................................................................. 26
6.2.1 About opening the units ........................................................................................................................................ 26
6.2.2 To open the outdoor unit ...................................................................................................................................... 26
6.2.3 To close the outdoor unit ...................................................................................................................................... 28
6.3 Mounting the outdoor unit .................................................................................................................................................... 29
6.3.1 About mounting the outdoor unit......................................................................................................................... 29
6.3.2 Precautions when mounting the outdoor unit...................................................................................................... 29
6.3.3 To provide the installation structure..................................................................................................................... 29
6.3.4 To install the outdoor unit ..................................................................................................................................... 30
6.3.5 To provide drainage ............................................................................................................................................... 30
6.3.6 To prevent the outdoor unit from falling over...................................................................................................... 32
6.1 Preparing the installation site
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
Choose an installation location with sufficient space to transport the unit in and
out of the site.
Do NOT install the unit in places often used as work place. In case of construction
works (e.g. grinding works) where a lot of dust is created, the unit MUST be
covered.
6.1.1 Installation site requirements of the outdoor unit
INFORMATION
Also read the following requirements:
General installation site requirements. See "2General safety precautions"[47].
Service space requirements. See "16Technical data"[472].
Refrigerant piping requirements (length, height difference). See
"7.1.1Refrigerant piping requirements"[433].
CAUTION
Appliance NOT accessible to the general public, install it in a secured area, protected
from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and
light industrial environment.