6 | Unit installation
Installer reference guide
27
RXA-B8, RXM-A(9), ARXM-A(9), RXP-N9, RXF-D(9), ARXF-A(9), RZAG-B
R32 split series
4P766272-2 – 2024.01
▪ Mind the service space requirements when installing the windbreaker.
a
b
c
d
c
d
a Sea wind
b Building
c Outdoor unit
d Windbreaker
The outdoor unit is designed for outdoor installation only and for ambient
temperatures specified in the table below (unless otherwise specified in the
operation manual of the connected indoor unit).
Model Cooling Heating
ARXM50, RXM50+60 –10~50°C DB –20~24°C DB
RXA, ARXF, ARXM60+71,
RXM71
–10~46°C DB –15~24°C DB
RXF, RXP –10~48°C DB –15~24°C DB
RZAG-B –20~52°C DB –20~24°C DB
6.1.2 Additional installation site requirements of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the outdoor unit
is NEVER snowed up.
a
b
c
c
d
a Snow cover or shed
b Pedestal
c Prevailing wind direction
d Air outlet
It is recommended to provide at least 150 mm of free space below the unit
(300mm for heavy snowfall areas). Additionally, make sure the unit is positioned at
least 100mm above the maximum expected level of snow. If necessary, construct
a pedestal. See "6.3Mounting the outdoor unit"[428] for more details.