14 | Maintenance and service
Installer reference guide
68
2MXM-A8, 3MXM-A8, 4MXM-A8, 5MXM-A8
R32 Split series
4P766272-5C – 2025.05
14 Maintenance and service
NOTICE
General maintenance/inspection checklist. Next to the maintenance instructions in
this chapter, a general maintenance/inspection checklist is also available on the
Daikin Business Portal (authentication required).
The general maintenance/inspection checklist is complementary to the instructions
in this chapter and can be used as a guideline and reporting template during
maintenance.
NOTICE
Maintenance MUST be done by an authorised installer or service agent.
We recommend performing maintenance at least once a year. However, applicable
legislation might require shorter maintenance intervals.
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes: GWP value of the
refrigerant × total refrigerant charge [in kg] / 1000
DANGER: RISK OF ELECTROCUTION
Disconnect the power supply for more than 10minutes, and measure the voltage at
the terminals of main circuit capacitors or electrical components before servicing.
The voltage MUST be less than 50VDC before you can touch electrical components.
For the location of the terminals, see the wiring diagram.
AC
DC
DC
S20 S21 S22 S23
S92
S93
S40
S80
S70
U W
V
DC-
FU2
S90
S24
AL2 AL1
e
f
g
h
a
b
c
d
DC(-)
FU2
a AL1, AL2 - solenoid valve lead wire connector*
b S20~24 - electronic expansion valve coil lead wire connector (room A, B, C, D, E)*
c S40 – thermal overload relay lead wire and high pressure switch connector*
d Multimeter (DC voltage range)
e S90~93 – thermistor lead wire connector
f S70 - fan motor lead wire connector
g S80 - 4-way valve lead wire connector
h Compressor lead wire connector
*May differ depending on the model.
14.1 Overview: Maintenance and service
This chapter contains information about: