Product Features:
Monitored (16/20A Models)
Technical Specifications
Model Name
PDU33101
PDU33104
PDU33121
PDU33401
PDU33102
PDU33103
Input
Nominal Voltage 208V 200-240V 346-415 V
Frequency 50/60Hz
Maximum Input Current 16A UL (Derated)
16A UL (Derated)
16A CE
Plug Type NEMA L21-20P NEMA L15-20P
IEC 309 16/20A Red
(3P+N+E)
Power Cord Type SR (12 AWG)
Power Cord Length 10 ft/3.05 m
Output
Nominal Voltage
120V
200-240V120/208V
120/208V
Maximum Output Current 16A UL (Derated)
16A UL (Derated)
16A CE
Outlet Type
(36)NEMA 5-20R
(30) IEC 320 C13 (6) IEC 320 C19
(24) NEMA 5-20R (6)
NEMA L6-20R
(2) NEMA 5-20R (36)
IEC 320 C13 (6) IEC 320
C19
Outlet Number
36
36
30
44
Management and Communications
Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software PowerPanel® Business Edition
Networking Yes
Serial Port RJ45
Sensor Capable Optional
Physical
Dimensions (H x W x D) 70.5" x 2.2" x 2.2" / 1790mm x 56mm x 55mm
Environmental
Humidity 0 to 95% Non-condensing
Altitude 11480 ft/3500 m
Temperature 23
o
F to 140
o
F / -5
o
C to 60
o
C
23
o
F to 131
o
F /
-5
o
C to 55
o
C
Safety Approvals
Certifications UL 60950-1, UL62368-1, FCC Class A
UL 60950-1, UL62368-1,
FCC Class A
CB, CE EN55032/24
Class A
* All specifications are subject to change without notice.
A. AC Inlet/ AC Power Cord - Used to connect PDU to utility
power or UPS.
B. AC Output Receptacles - Provides power for connected
equipment.
C. Status Indicator - Indicates the condition of the PDU (eg.
load or environment status).
D. Multifunction LCD Readout - Displays various PDU
information such as power and load condition.
E. Ethernet Port – Used to connect PDU to the network.
F. ENVIROSENSOR/ Daisy Chain (In) Port (RJ45 modular port)
– Used for ENVIROSENSOR or chaining to previous PDU.
G. USB Port - Used to upgrade the firmware via a flash drive.
H. Serial Port (RJ45 modular port) - Used to connect to a PC
and control the PDU locally via SSH/Telnet.
I. Daisy Chain (Out) Port – Used for chaining to next PDU.
J. Select Button - Used to control the LCD screen and toggle
through the available information options.
K. Enter Button - Used to choose selected items, enter to next
level menu or return to previous menu.
L. Bracket Screw Hole - Used to secure the Mounting Pegs (pre-
installed) or Mounting Brackets.