Crestron Green Light GLXX-2DIM8 handleiding

24 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 23 van 24
Crestron Green Light Express™ Dimming Panel
Crestron Network to Mini Network Interconnect Diagram
24
Y
Z
G
To Mini Network Device
Front
View
Front
View
To Network Device
24
Y
Z
G
Black
Blue
White
Red
Shield*
Red
White
Blue
Black
Wire Nuts &
Jumper Wires
Pair A
22 AWG Twisted
Blue = Z
White = Y
Pair B
18 AWG Parallel
Black = Ground
Red = 24 VDC
To Control System
G
Z
Y
24
Front
View
Black
Green
Green
CAUTION: Possible Equipment Damage if Miswired
Do not power up system until all wiring is verified. Care should be taken to ensure Data (Y & Z), and Power
(24 & G) connections are not crossed.
Ground Shield at the Control System end only.
Model CNTBLOCK network terminal expander and diagnostic tool for the Cresnet system is recommended for
testing purposes and wiring convenience.
Jumper wires: Use #18 AWG. Use a wire nut that accommodates all three wires.
NOTE: Crestron recommends the use of C2N-HBLOCK or CNTBLOCK as the preferred method to daisy chain or
expand the Cresnet network. If the blocks are not available, use the method as shown.
Installation Guide – DOC. 6889B Crestron Green Light Express™ Dimming Panel 23