Terminal Block with Breaker Crestron CLTIBN
Terminal Block to Module Wiring Diagrams
With the branch circuit breakers and the terminal block circuit breakers turned off, connect the circuit feed (LINE and
NEUTRAL) and controlled circuit (LOAD) wires to the terminal blocks per the markings provided on the wiring labels (as
shown in the following diagrams). Wires should be stripped to 12 mm. Terminal blocks accept one 2.5 - 6.0 mm
2
wire and
should be tightened to 1 Nm. Circuit breaker lugs accept up to one 16 mm
2
wire and should be tightened to 1.2 Nm.
NOTE: Illustrations are provided for installation on the right and left sides of a CAENIB enclosure. Illustrations show the
terminal block with the cover plate removed.
CLTIBN-1DIM4 to CLXI-1DIM4
Wiring of CLTIBN-1DIM4 Terminal Block and CLXI-1DIM4 (Single-wide and Left Side Double-wide Enclosures)
LINE
TO LOAD 1
TO LOAD 1
TO LOAD 2
TO LOAD 2
TO LOAD 3
TO LOAD 3
TO LOAD 4
TO LOAD 4
NEUTRAL
FACTORY INSTALLED
JUMPER WIRE
DO NOT REMOVE
BROWN
RED
RED
RED
RED
BLUE
Wiring of CLTIBN-1DIM4 Terminal Block and CLXI-1DIM4 (Right Side Double-wide Enclosures)
FACTORY INSTALLED
JUMPER WIRE
DO NOT REMOVE
TO LOAD 1
TO LOAD 1
TO LOAD 2
TO LOAD 2
TO LOAD 3
TO LOAD 3
NEUTRAL
TO LOAD 4
TO LOAD 4
LINE
BLUE
RED
RED
RED
RED
BROWN
4 Terminal Block: CLTIBN Installation Guide – DOC. 6561A